Installation Procedure
CAUTION
• Only in the Cool mode, you can check the correct
operation of the drain pump.
When the electric cable connection has not been
completed
• Remove the control box cover of the indoor unit.
• Connect the power supply to the L and N
terminals.
• Reassemble the control box cover and turn on the
indoor unit.
CAUTION
• When the float switch is not detected due to
insufficient water on the drain pan, the drain
pump will not work.
• If the power supply is directly connected to the L
and N terminals, communication error message
might appear.
• After completing the drainage check, turn the
unit off and disconnect the power supply.
• Reassemble the control box cover.
c Check whether the drain pump works correctly.
d Check whether the drainage is performing correctly at
the end of the drain pipe.
e Check for leakage at the drain pipe and drain pipe
connection part.
f When leakage occurs, check whether the indoor
unit is level and check the drain hose connection
part, drainpipe connection part and drain pump
connection.
g When the drainage check is completed and the
condensed water remains on the drain pan, remove
the water.
Step 12 Connecting the power and
communication cables
CAUTION
• Always remember to connect the refrigerant pipes before
performing the electric connections.
When disconnecting the system, always disconnect the
e
l
ectric cables before disconnecting the refrigerant pipes.
• For the product that uses the R-32 refrigerant, be
cautious not to generate a spark by keeping the
following requirements:
– Do not remove the fuses with power on.
– Do not disconnect the power plug from the wall outlet with
power on.
– It is recommended to locate the outlet in a high position.
Place the cords so that they are not tangled.
• Always remember to connect the air conditioner to the
grounding system before performing the electric connections.
Use a crimp ring terminal at the end of each wire.
The indoor unit is powered through the outdoor unit by
means of a H05RN-F (60245 / IEC57) connection cable (or a
more power model), with insulation in synthetic rubber and a
jacket in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.
1 Remove the screw on the electrical component box and
remove the cover plate.
2 Route the connection cord through the side of the indoor
unit and connect the cable to the terminals refer to the
figure below.
3 Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
4 Reassemble the electrical component box cover, carefully
tightening the screw.
1 Way Cassette (1 phase)
1(L) 2(N)
L
N
F1 F2
Outdoor Unit
Cable clamp
Cable clamp
Outdoor to indoor power cable
Main power cable
Communication
cable
Indoor Unit
L
N
F1
F2
DB68-13503A-01_IM_CAC R-32 WindFree1_4way_EA_EN_.indd 23DB68-13503A-01_IM_CAC R-32 WindFree1_4way_EA_EN_.indd 23 2025-04-08 오전 8:53:222025-04-08 오전 8:53:22