English
Installation Procedure
CAUTION
Check that the indoor unit is level with the ceiling by using
the leveller.
Install air ventilation to drain condensation smoothly.
Air ventilation
Ceiling
If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm from
the drain hose port. If it is raised higher than 550 mm,
there may be water leaks.
Band joint
Drain hose
Ceiling
20 mm or more
300 mm or less
550 mm or less
1/100 or more
Do not give the hose an upward gradient beyond the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
Under gradient
Ceiling
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as close
to the unit as possible.
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
Install horizontally.
Be horizontal
Indoor unit
Flexible hose
Max. allowable axis gap.
Indoor unit
Max. 20 mm
Max. allowable bending angle.
Indoor unit
Max. 30°