Samsung AC024TXQREH handleiding

34 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 22 van 34
22
Installation Procedure
English
Installation Procedure
1 Connect each assembly pipe to the appropriate valve
on the outdoor unit and tighten the flare nut.
2 Referring to the illustration below, tighten the flare
nut on section D first manually and then with a torque
wrench, applying the following torque.
Outer Diameter (D) ƟͱθαЇʪ࣍Ęଗ࣎
ø 6.35 14 to 18
ø 9.52 34 to 42
ø 12.70 49 to 61
ø 15.88 68 to 82
ø 19.05 100 to 120
A (Gas)
B (Liquid)
C
D
3 Connect the charging hose of low pressure side of
manifold gauge to the packed valve having a service
port as shown at the figure.
CAUTION
The designs and shape are subject to change
according to the model.
4 Open the valve of the low pressure side(A) of manifold
gauge anticlockwise.
AC018/024TXQREH
A (Gas)
B (liquid)
Vacuum pump
AC036/048/060TXQR*H
Outdoor Unit
Vacuum
Pump
A (Gas)
B (liquid)
ki]_TW`ZZ`hTWYptwhjG⴬⢰㫴G㐘㞬ὤG㢨㬅䏬䑀䇘㏘䇸pxluUGGGYY YWYWTXYTW`GGG㝘㤸GXXa[`a[Y