Samsung AC024MXADKH handleiding

28 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 24 van 28
24
Extra Procedures
English
Extra Procedures
3 Tighten the cap securely.
Outer Diameter
(mm)
Tightening torque
Body cap (N•m)
Charging port cap
(N•m)
Ø6.35
20 to 25
10 to 12
Ø9.52
20 to 25
Ø12.70
25 to 30
Ø15.88
30 to 35
Over Ø19.05
35 to 40
(1 Nm=10 kgfcm)
NOTE
Do not apply excessive force to the stop valve and
always use special instruments. Otherwise, the
stopping box can be damaged and the back sheet can
leaks.
If the watertight sheet leaks, turn the axis back by
half, tighten the stopping box, then check the leakage
again. If there is no leakage any more, tighten the
axis entirely.
Closing the stop valve
1 Remove the cap.
2 Turn the stop valve clockwise by using a hexagonal
wrench.
3 Tighten the axis until the valve reached the sealing
point.
4 Tighten the cap securely.
CAUTION
When you use the service port, always use a charging
hose, too.
Check the leakage of refrigerant gas after tightening
the cap.
Must use a spanner and wrench when you open/
tighten the stop valve.

Bekijk gratis de handleiding van Samsung AC024MXADKH, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSamsung
ModelAC024MXADKH
CategorieAirco
TaalNederlands
Grootte4977 MB