Installation Procedure
English
Installation Procedure
3 Connectthecharginghoseoflowpressureside
ofmanifoldgaugetothepackedvalvehavinga
serviceportasshownatthefigure.
CAUTION
Thedesignsandshapearesubjecttochange
accordingtothemodel.
4 Openthevalveofthelowpressureside(A)of
manifoldgaugeanticlockwise.
Vacuum
pump
A(Gas)
B(liquid)
5 Purgetheairfromthesystemusingvacuumpump
forabout10minutes.
Closethevalveofthelowpressuresideof
manifoldgaugeclockwise.
Makesurethatpressuregaugeshows-0.1
MPa(-76cmHg)afterabout10minutes.This
procedureisveryimportanttoavoidagasleak.
Turnoffthevacuumpump.
Removethehoseofthelowpressuresideofmanifold
gauge.
6 Openthestopvalveofbothliquidandgassides.
7 Mountthevalvestemnutsandtheserviceport
captothevalve,andtightenthematthetorqueof
183kgfꞏcmwithatorquewrench.
8 Checkforgasleakage.
Atthistime,especiallycheckforgasleakagefrom
the3-wayvalve’sstemnuts(Aport),andfromthe
serviceportcap.
CAUTION
Connecttheindoorandoutdoorunitsusingpipes
withflaredconnections(notsupplied).Forthe
lines,useinsulated,unwelded,degreasedand
deoxidizedcopperpipe,(CuDHPtypetoISO1337or
UNIEN12735-1),suitableforoperatingpressures
ofatleast4200kPaandforaburstpressureofat
least20700kPa.Copperpipeforhydro-sanitary
applicationsiscompletelyunsuitable.
Forsizingandlimits(heightdifference,line
length,max.bends,refrigerantcharge,etc.)see
“Connectingrefrigerantpipesection”.
Step 8 Performing the gas leak test
LEAK TEST WITH NITROGEN (before opening valves)
Inordertodetectbasicrefrigerantleaks,before
recreatingthevacuumandrecirculatingtheR-410A,
itistheresponsibilityoftheinstallertopressurize
thewholesystemwithnitrogen(usingacylinderwith
pressurereducer)atapressureabove0.2MPa,less
than4MPa(gauge).
LEAK TEST WITH R-410A (after opening valves)
Beforeopeningvalves,dischargeallthenitrogeninto
thesystemandcreatevacuum.Afteropeningvalves
checkleaksusingaleakdetectorforrefrigerantR-410A.
Onceyouhavecompletedalltheconnections,check
forpossibleleaksusingleakdetectorspecifically
designedforHFCrefrigerants.
A(Gas)
B(Liquid)
Thedesignsandshapearesubjecttochange
accordingtothemodel.
Step 9 Connecting the drain hose to
the outdoor unit
Whenusingtheairconditionerintheheatingmode,
icemayaccumulate.Duringde-icing(defrost
operation),thecondensedwatermustbedrainedoff
safely.Consequently,youmustinstalladrainhoseon
theoutdoorunit,followingtheinstructionsbelow.
1 Makespacemorethan80mmbetweenthe
bottomoftheoutdoorunitandthegroundfor
installationofthedrainhose,asshowninfigure.