8 OM-SERVING LINES
DANFOSS CONTROLLER CODES
DISPLAYED
ALARM CODE
ALARM ACTION
Hi High Temperature Alarm
Inspect door/drawer sealing
Contact service
Lo Low Temperature Alarm Contact service
CON
Condenser Temperature
High Limit
Clean condenser coil
Inspect coil for any objects
obstruction hindering airow
Contact service
uHi Line Voltage Too High
Verify voltage of power source,
to be performed by qualied
technician
Contact service
uLi Line Voltage Too Low
Verify voltage of power source,
to be performed by qualied
technician
Contact service
LEA
Continuous Compressor
Runtime
Inspect door/drawer sealing
Inspect condenser coil, clean if
necessary
Contact service
E01 S1 Sensor Failure Contact service
E02 S2 Sensor Failure Contact service
E03 S3 Sensor Failure Contact service
E04 S4 Sensor Failure Contact service
SERVICE - COLD
CAUTION: COMPONENT PARTS SHALL BE REPLACED WITH FACTORY OEM PARTS.
SERVICE WORK SHALL BE DONE BY FACTORY AUTHORIZED SERVICE
PERSONNEL, SO AS TO MINIMIZE THE RISK OF POSSIBLE IGNITION DUE TO
INCORRECT PARTS OR IMPROPER SERVICE.
CAUTION: BEFORE MAKING ANY REPAIRS, ENSURE THE UNIT IS DISCONNECTED
FROM ITS POWER SOURCE.
This piece of equipment uses a R290 Refrigeration system. This equipment has
been clearly marked on the serial tag the type of refrigerant that is being used.
There is also a warning labels stating that the unit contains R290 refrigerant. R290
is safe to use as long as you follow these warning labels.
No smoking or open ames when servicing this equipment. If needed, use a CO2
or dry-powder type re extinguisher.
Replacement parts used on any R290 Refrigeration system cabinet must have
specic UL certication for non-sparking components.
Only authorized service technician, certied in R290 system should service this
equipment.
MANIFOLD SET
A R134A manifold set can be used for servicing this equipment.
REFRIGERANT RECOVERY
Follow all national and local regulations for R-290 refrigerant recovery.
LEAKING CHECKING AND REPAIR
Leak check an R-290 system the same way you would an R-134a or R-404A
system with the following exceptions.
1. Do not use a Halid leak detector on a R290 system.
2. Electronic leak detector must be designated specically for combustible gas.
Use of a bubble solution or an ultrasonic leak detector are acceptable.
When repairing a leak, it is recommended using oxygen free dry nitrogen with a
trace gas not exceeding 200PSI.
When accessing an R290 system, piercing valves are not to remain on the
equipment in a permanent manner. After charge is recovered, Schrader valves
are to be installed on the process stubs. Proper charge is to be weighed into the
system and the system is to be leak checked afterwards.
The R290 equipment must have red process tubes and other devices through
which the refrigerant is serviced, such as any service port. This color marking must
remain on the equipment. If marking is removed, it must be replace and extend at
least 2.5 centimeters (1”) from the compressor.
CHARGING
Follow the charge amount specied on the data tag. It is recommended to use the
shortest hoses possible to prevent undercharging.
Ensure the system is sealed and leak checked
Evacuate system to a minimum 500 micron
Weigh in correct charge
Leak check the system again
Bleed the refrigerant from the high side hose to the low side hose
Disconnect the hoses
Remove line taps