Pro1 T725 handleiding
Handleiding
Je bekijkt pagina 2 van 4

Thermostat Quick Reference
Wiring
Tech Settings Tech Settings
This thermostat has a technician setup menu for easy installer 
conguration. To setup the thermostat for your particular application:
Swing Setting Tip
Temperature swing, sometimes called dierential or cycle rate, can be customized 
for this individual application.  For most applications choose a swing setting that is 
as long as possible without making the occupants uncomfortable.
Technician Setup Menu
LCD Will Show
The compressor short cycle delay 
protects the compressor from 
short cycling. This feature will not 
allow the compressor to be turned 
on for 5 minutes after it was last 
turned o.
Selecting “ON” will not allow 
the compressor to be turned on 
for 5 minutes after the last time 
the compressor was switched 
o. Select “OFF” to remove this 
delay.
0
This feature allows the installer 
to change the calibration of the 
room temperature display. For 
example, if the thermostat reads 
70˚ degrees and you would like it 
to read 72˚ then select +2.
Room 
Temperature 
Calibration
You can adjust the room 
temperature display to read 
4˚above or below the factory 
calibrated reading.
Tech Settings
Adjustment Options
Compressor
Short Cycle
Delay
Default
0N
Cd
0.8
The swing setting often called 
“cycle  rate”, “dierential” or “
anticipation” is adjustable.  A 
smaller swing setting will cause 
more frequent cycles and a larger 
swing setting will cause fewer 
cycles.
Cooling 
Swing
The cooling swing setting is 
adjustable from 0.2˚ to 2˚.  For 
example: A swing setting of 
0.5˚ will turn the cooling on at 
approximately 0.5˚ above the 
setpoint and turn the cooling 
o at approximately 0.5˚ below 
the setpoint.
0FF
This feature will ash “FILT” in the 
display after the elapsed run time 
to remind the user to change the 
lter. A setting of “OFF” will disable 
this feature.
Filter Change
Reminder
You can adjust the lter change 
reminder from OFF to 2000 
hours of runtime in 50 hour 
increments.Tap the second 
button from the top left side of 
the thermostat to display the 
current lter elapsed runtime.
F1
Next Step
Prev Step
100
SE
0
Next Step
Prev Step
CAL
Next Step
Prev Step
Next Step
Prev Step
Use the           or           keys to change settings and the NEXT STEP or 
PREV STEP key to move from one step to another. Note: Only press 
the DONE key when you want to exit the Technician Setup options.
1.  Press the MENU button
2.  Press and hold TECH SET button for 3 seconds. This 3 second 
     delay is designed so that homeowners do not accidentally access
     the installer settings.
3. Congure the installer options as desired using the table below.
Tech Settings
Adjustment Options Default
The swing setting often called “cycle 
rate”, “dierential” or “anticipation” 
is adjustable.  A smaller swing 
setting will cause more frequent 
cycles and a larger swing setting 
will cause fewer cycles.
The heating swing setting is 
adjustable from 0.2˚ to 2˚. For 
example: A swing setting of 
0.5˚ will turn the heating on at 
approximately 0.5˚ below the 
setpoint and turn the heating 
o at approximately 0.5˚ above 
the setpoint.
Heating
 Swing
0.8
Next Step
Prev Step
This feature allows you to set a 
minimum cool setpoint value. The 
setpoint temperature cannot be 
lowered below this value.
Cooling 
Setpoint
Limit
44
Use the         and          key to 
select the minimum cool 
setpoint.
This feature allows you to set a 
maximum heat setpoint value. The 
setpoint temperature cannot be 
raised above this value.
Heating 
Setpoint
Limit
90
Use the         and          key to 
select the maximum heat 
setpoint.
Next Step
Prev Step
Next Step
Prev Step
CO L
Select F for Fahenheit temperature 
read out or select C for Celsius 
read out.
F for Fahrenheit
C for Celsius
F or C
F
F
FC
You can select either a 12 or 24 hour 
clock setting.
12 or 24 
Hour Clock
12
Use the         and          to select 12 
or 24 hour clock.
Next Step
Prev Step
Next Step
Prev Step
HE L
dFHE
LCD Will Show
The low battery indicator is displayed when the AA battery power is low. If the user 
fails to replace the battery within 21 days, the screen will only show the low battery 
indicator but maintain all functionality.  If the user fails to replace the batteries after 
an additional 21 days (days 22-42 since rst “low battery” display) the setpoints will 
change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from 
either of these, it will hold for 4 hours then return to either 55˚F or 85˚F.  After day 63 
the batteries must be replaced immediately to avoid freezing or overheating because 
the thermostat will shut the unit o until the batteries are changed.
Important
Indicates the current room temperature
Time and day of the week
Setpoint: Displays the user selectable setpoint temperature.
Hold is displayed when the thermostat program is permanently overridden.
System Operation Indicators:
The COOL ON, HEAT ON or        icon will display when the COOL, HEAT, or       (fan) is on.
Note: The Compressor delay feature is active if these are ashing.
Low Battery Indicator: Replace batteries when this indicator is shown.
Button Options
Program Time Periods: This thermostat has 4 programmable time periods 
per day.
Getting to know your thermostat
Hold
LOW
    COOL ON
EmHEAT ON
Sun Mon Tue Wed Thu Fri Sat
Temperature
Tech Set
Next Step
Set Time
Run Sched
Set Sched 
Hold
Prev Step
Menu
Done
LEAVE     SLEEP
     RETURN    WAKE
Stage 1 & 2
Stages: Indicates the stages of heat that are active.
Caution: 
Electrical Hazard
All components of the 
control system and the 
thermostat installation must 
conform to Class II circuits 
per the NEC Code.
Warning:
Do not overtighten terminal 
block screws, as this can 
damage the terminal block.  
A damaged terminal block 
can keep the thermostat 
from tting on the subbase 
correctly or cause system 
operation issues.
Installation Tip
Max Torque = 6in-lbs.
Wiring
If you are replacing a thermostat, 
make note of the terminal 
connections on the thermostat 
that is being replaced.  In some 
cases the wiring connections will 
not be color coded. For example, 
the green wire may not be 
connected to the G terminal.
Loosen the terminal block 
screws. Insert wires then 
retighten terminal block screws.
Place nonammable insulation 
into wall opening to prevent 
drafts.
1.
2.
3.
Terminal Designations
R
Failure to disconnect the power 
before beginning to install this 
product can cause electrical 
shock or equipment damage.
C
B
O
G
W/E
W2
Y
Heat Pump System
1 HEAT 1 COOL / 2 HEAT 1 COOL
Conventional System
1 HEAT 1 COOL / 2 HEAT 1 COOL
Transformer Power
Transformer Common
Changeover Valve 
Energized in HEAT
Fan Relay
First Stage of Emergency HEAT
Changeover Valve 
Energized in COOL
Second Stage of HEAT/
EMERGENCY HEAT
First Stage of HEAT and COOL
Transformer Power
Transformer Common
Fan Relay
First Stage of HEAT
Second Stage of HEAT
First Stage of COOL
Energized in HEAT
Energized in COOL
1
2
3
7
8
1
3
2
7
8
Bekijk gratis de handleiding van Pro1 T725, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Pro1 | 
| Model | T725 | 
| Categorie | Niet gecategoriseerd | 
| Taal | Nederlands | 
| Grootte | 1055 MB | 
