UPS Status Display String Description:
The following table shows the description of the LCD display string:
Table4. UPS Status Display String
LCD Display String
Description
STbY
UPS work at Standby mode
IPVL
Input voltage is too low
IPVH
Input voltage is too high
IPFL
Input frequency is too low
IPFH
Input frequency is too high
NORM
UPS work at Line mode
AVR
UPS work at AVR mode
bATT
UPS work at Battery mode
TEST
UPS work at battery life/function test mode
OPVH
Battery mode, the output is too high
OPVL
Battery mode, the output is too low
OPST
Output short
OVLD
Overload
bATH
Battery voltage is too high
bATL
Battery voltage is too low
OVTP
Internal temperature is too high
FNLK
Fan is locked
bTWK
Batteries are weak
User Setting String Description:
The following table shows the options that can be changed by user.
Table5. User Setting String
OPV
Output voltage mode
select
[220]= 220V
[230]= 230V
[240]= 240V
AVR Input type select
[000]= Normal range mode
[001]= Wide range mode
[002]= Generator mode
EbM
External battery module
(EBM)
0~9 is the number of external battery
module
TEST
Auto self-test
[000]=Disable [001]=Enable
AR
Automatic restart
[000]=Disable [001]=Enable
GF
Green function
[000]=Disable [001]=Enable
bZ
Buzzer control
[000]=Disable [001]=Enable
LS1
Load segment 1
[000]=Turn off [001]=Turn on
LS2
Load segment 2
[000]=Turn off [001]=Turn on
Bekijk gratis de handleiding van PowerWalker VI 1500 RT HID, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.