Handleiding
Je bekijkt pagina 5 van 67

2
★ An appropriate disconnect device as short-circuit backup
protection should be provided in the building wiring installation.
★ For three-phase equipment connection to an IT power system, a
four-pole device which disconnect all phase conductors and the
neutral conductor should be provided in the building wiring
installation.
★ This is permanently connected equipment, it must be installed
by qualified maintenance personnel.
★ Earth connection essential before connecting to the building
wiring terminal.
1.2 Operation
★ Do not disconnect the earth conductor cable on the UPS or the
building wiring terminals in any time since this would cancel the
protective earthing of the UPS system and of all connected loads.
★ The UPS output terminal block may be electrically lived even if
the UPS system is not connected to the building wiring terminal.
★ In order to fully disconnect the UPS, turn the M1/M2/N input
breaker in the “OFF” position (for PowerWalker VFI 10000-20000
TP 3/1), turn the R/S/T/N input switch in the “OFF” position (for
PowerWalker VFI 10000TCP 3/1), then disconnect the mains lead.
★ Ensure that no liquid or other foreign objects can enter the UPS.