PowerWalker Solar Inverter 3600 SKY handleiding

75 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 21 van 75
19
3
rd
party Lithium battery If selected, programs of 11, 17, 18
and 19 will be automatically set up.
No need for further setting. Please
contact the battery supplier for
installation procedure.
17
Bulk charging voltage
(C.V voltage)
Default setting: 56.4V
If self-defined is selected in program
14, this program can be set up.
Setting range is from 48.0V to 64.0V.
Increment of each click is 0.1V.
18
Floating charging
voltage
Default setting: 54.0V
If self-defined is selected in program
14, this program can be set up.
Setting range is from 48.0V to 64.0V.
Increment of each click is 0.1V.
19
Low DC cut off battery
voltage setting
Default setting: 40.8V
If self-defined is selected in program
14, this program can be set up.
Setting range is from 40.8V to 48.0V.
Increment of each click is 0.1V. Low
DC cut-off voltage will be fixed to
setting value no matter what
percentage of load is connected.
20
Battery stop
discharging voltage
when grid is available
default setting: 46V
Setting range is from 44V to 51V and
increment of each click is 1V.
10% (default) If “WECO battery” is selected in
program 14, the parameter will be
fixed at 10% SOC of batter y.
21
Battery stop charging
voltage when grid is
available
Battery fully charged
The setting range is from 48V to 58V
and increment of each click is 1V.
Default setting: 54V
15% (default) If “WECO battery” is selected in
program 14, this parameter will refer
to the SOC of battery and adjustable
from 15 to 100%. Increment of each
click is 5%.