33 Battery equalization
If “Flooded” or “User-Defined” is selected in program 05, this program
can be set up.
Battery equalization Battery equalization disable
(Default)
34
Battery equalization
voltage
58.4V (Default)
Se
tting range is from 48V to 64V.
Increment of each click is 0.1V.
35 Battery equalized time
60min (Default)
Se
tting range is from 5min to
900min. Increment of each click is
5min.
36
Battery equalized
timeout
120min (Default)
Se
tting range is from 5min to 900
min. Increment of each click is 5
min.
37 Equalization interval
30days (Default)
Setting range is from 0 to 90 days.
Increment of each click is 1 day