PowerWalker Solar Inverter 3600 LGT handleiding

85 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 21 van 85
19
5% (default)
If
“WECO battery” is selected
in program 05, the setting
value will be fixed at 5% of
connected battery capacity.
13
Setting voltage point
back to battery mode
when selecting SBU”
(SBU priority) in
program 01.
Setting range is FUL and from 48V to 64V. Increment of each click is
1 V.
Battery fully charged
54V (default)
10% (default) If “WECO battery” is selected in
program 5, this parameter value
will be displayed in percentage and
value setting is based on battery
capacity percentage. The setting
range is from 10%to 100%.
Increment of each click is 5%.
14
Lithium battery turn-on
when the device is
powered on.
Auto turn-on disable(default) Auto turn-on enable
15
Lithium battery turn-on
immediately
NOTE:
This setting is
effective only when
program 14 is
set as
“enable”.
Turn-on immediately
disable(default)
Turn-on immediately enable
16
Charger source
priority:
If this inverter/charger is working in Line, Standby or Fault mode,
charger source can be programmed as below:

Bekijk gratis de handleiding van PowerWalker Solar Inverter 3600 LGT, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.