PowerWalker LiFe Battery System 102-37 handleiding
Handleiding
Je bekijkt pagina 49 van 50

~ 48 ~
button is blinking
red
Protection against over-
temperature or under-temperature
(cell temperature is lower than
0 °C or higher than 55 °C).
Check the battery pack
temperature via the inverter’s
APP.
If the battery pack temperature is
higher than 55°C, wait for the
temperature to drop to 50°C.
If the battery pack temperature is
lower than -20°C, wait for the
temperature to rise to -10°C
Protection against over current
Set a lower charging power limit
for the inverter, and wait for 60
seconds
The status LED in
the power button
is steady red
Major
Cells failure.
The contactor in the battery pack
failed.
Battery pack EOL;
Contact supplier for service
Table 12 Troubleshooting list
Bekijk gratis de handleiding van PowerWalker LiFe Battery System 102-37, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | PowerWalker |
| Model | LiFe Battery System 102-37 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 4546 MB |





