Alert Code Alert Text Description Possible Causes & Remedies
4.1
WLS ERR The water level sen-
sor appears to be
malfunctioning.
1. Disconnect power and check the water level sen-
sor connector. Clean and reconnect.
2. Replace water level sensor if necessary.
4.2
WATER LOW The water level is get-
ting very low.
Rell the water reservoir soon.
4.3
NO WATER The water level is too
low to continue cooling.
Rell the water reservoir to continue normal operation.
4.4
OVER FILL The water level ap-
pears to be too high.
1. Shut off the water supply.
2. Check that the oat shutoff valve is positioned
straight up and down, adjust if necessary.
3. Turn on the water supply and check for leaks when
the oat is in the top (off) position. Replace if
necessary.
5.7
EXIT T ERR The Exit Temperature
Sensor is not func-
tioning correctly.
The exit air temperature sensor is located in the wiring
harness of the water level sensor.
1. Disconnect power and check the water level sensor
connector. Clean and reconnect.
2. Replace water level sensor if necessary.
ALERT CODES