ALERT CODES
Alert Code Alert Text Description Possible Causes & Remedies
1.2
Cont.
FAN ERR The load on the fan is
higher than expected
2. If an extension cord is being used, make sure it
meets the size and length requirements in the
Safety section of this manual. Remove/replace if
necessary.
3. Have a certied electrician inspect the wall outlet
circuit.
2.1 PUMP ERR The pump does not
appear to be running
as intended
1. Turn cooling mode to Max Cooling and listen for
water circulation and look for proper media wet-
ting. If water is not circulating, disconnect power
and proceed to step 2.
2. Check for broken or pinched wires or connectors.
If wires are damaged do not attempt to repair, in-
stead replace the pump.
3. Check the pump connector attachment to the con-
trol module to ensure the t is snug. Unplug and
clean out terminals if necessary. Plug in and re-
check pump operation. Replace the pump if nec-
essary.
2.2
PUMP ERR The load on the pump
is higher than expected
1. If an extension cord is being used, make sure it
meets the size and length requirements in the
Safety section of This manual. Remove/replace if
necessary.