Air Conditioner Service Manual
26
Installation Safety Precautions
1) Select the installation location according to the requirements of this manual. (See the requirements in the
Installation section).
2) Handle unit transportation with care. The unit should not be carried by only one person if it is more than 44lbs.
3) When installing the indoor and outdoor units, a sufficient fixing bolt must be installed, ensuring the
installation supporter is firm.
4) Wear a safety belt if the working height is above 7ft.
5) Use equipped or appointed components during installation.
6) Make sure no foreign objects are left in the unit after finishing installation.
Improper installation may lead to fire hazard, explosion, electric shock, or injury.
Safety precautions for installing and relocating the unit.
To ensure safety, be mindful of the following precautions.
Warnings
1) When installing or relocating the unit, ensure the refrigerant circuit is purged and free from air and other
contaminants. Any presence of air or other foreign substances in the refrigerant circuit will cause system
pressure rise or compressor rupture, resulting in injury.
2) Do not charge the unit with refrigerant that does not comply with the nameplate or with unqualified
refrigerant during installation or relocation. Otherwise, it may cause abnormal operations, wrong actions,
mechanical malfunctions, or even series safety accidents.
3) When refrigerant needs to be recovered during relocating or repairing the unit, confirm the unit is running is
Cooling mode. Then, fully close the valve at the high-pressure side (2-way valve). About 30-40s later, fully
close the valve at the low-pressure side (3-way valve). Immediately stop the unit and disconnect the power.
Note: The time for refrigerant recover should not exceed 1 min. If refrigerant recovery takes too long, it may
cause the compressor to overheat, resulting in injury.
4) During refrigerant recovery, ensure that both 2-way and 3-way valves are fully closed and power is
disconnected before detaching the connecting the pipe. If the compressor starts running when the valve is
open and the connecting pipe is not yet connected, air will be sucked in, which can cause the pressure to rise,
potentially leading to compressor overheating or a gas leak.