PHOENIX CONTACT 105608_en_02
4.4 Technical data
Voltage measurement SCK-M-U-1500V (item no. 2903591)
Supply
Supply voltage 24 V DC (-10% … +25%) or via
SCK-M-I-8S-20A
Typical internal current consumption 8 mA
Maximum internal current consumption 65 mA
Measuring inputs
Voltage measuring range 0 V DC ... 1500 V DC (CAT III)
0 VDC ... 1000 VDC (UL)
Maximum transmission error from measur-
ing range final value
1% after additional compensation
(valid for 100 V DC ... 1500 V DC)
Temperature coefficient from T >25°C 0.01%/K
Number of measuring channels 1
Connection method Screw connection
Minimum terminal block distance 32 mm
Transient overvoltage 6 kV
Analog output
Output voltage range 2 V … 10 V
Cable length (for 0.15 mm²) 0.5 m, maximum
Cable type Twisted, shielded
Load 10 kΩ
Transient period 300 ms
General data
Degree of protection IP20
Protective circuit Surge protection (33 V suppressor diode)
Ambient temperature range (operating) -20°C ... 70°C
Ambient temperature range (storage) -40°C ... 85°C
Dimensions W / H / D 22.5 mm / 102 mm / 128.5 mm
Screw connection rigid / flexible / AWG 0.2 mm ...2.5 mm² / 0.2mm ... 2.5 mm² / 24 ... 12
Tightening torque 0.5 Nm ... 0.6 Nm
Humidity at 25°C, non-condensing ≤95%
Altitude ≤2000 m
DIN rail installation 35 mm (DIN EN 50022)
Pollution degree 2
Conformance/approvals
Conformance CE-compliant
Conformance with EMC Directive and Low
Voltage Directive
Referenced standard EN 61010-01
EN 61010-2-30