Control Input
107309_en_02 PHOENIX CONTACT 31 / 36
9.2 Closed active
If the Closed active radio button is activated, the power supply is switched on if:
You connect a resistor less than 1.5 kbetween signal contacts Rem and SGnd
Signal contacts Rem and SGnd are short circuited or
A voltage source is connected between signal contacts Rem and SGnd which supplies
a voltage in the range from 0 V to 5 V DC
Figure 9-4 Closed active – power supply ON
The power supply can then be switched off on the secondary side if:
You connect a resistor greater than 1.5 kbetween signal contacts Rem and SGnd
Signal contacts Rem and SGnd are open or
A voltage source is connected between signal contacts Rem and SGnd which supplies
a voltage in the range from 10 V to 24 V DC
Figure 9-5 Closed active – SLEEP MODE