Power manual for signal conditioners and MINI Analog, MINI Analog Pro, MACX Analog measuring transducers
30 / 56 Phoenix Contact
105810_en_02
Example for supply via a MINI MCR-2-PTB… power terminal
The goal is to supply 32 MINI MCR-2-RTD-UI temperature measuring transducers
(item no. 2902049), ten configurable MINI MCR-2-UI-UI signal conditioners
(item no. 2902037), with 4 mA ... 20 mA current output and 40 universal
MINI MCR-2-UNI-UI-UIRO signal conditioners with switching output (item no. 2902026)
at an operating voltage of 24 V DC.
First determine the current consumption of the modules from the packing slips. For the
temperature measuring transducers it is 31.5 mA per module and for the configurable
transducers it is 25 mA at the desired current output. The universal signal conditioners
with switching output require 31.5 mA each.
Then determine the maximum total current consumption of all 82 modules.
The total current consumption of 2518 mA is less than the maximum permissible current
for supply via the MINI MCR-2-PTB…. The fuses connected upstream of both power
modules should each have a nominal current of 4000 mA. To ensure that the fuses
definitely trip in the event of a short circuit, the 24 V DC supply in this example is provided
by a QUINT4-PS/1AC/24DC/3.8/SC (item no. 2904599). The structure is shown in
Figure 4-5 on page 31. The wiring is as shown in Figure 4-4 on page 29.