96 / 188 Phoenix Contact
6452_en_11
9.1.4 Indicators on I/O terminals
In this section, I/O terminals are all terminals that acquire or output signals, i.e., all
terminals excluding bus couplers, power, segment, and power-level terminals.
The LEDs of the I/O terminals are electrically located in the logic area.
This may mean that the LED of an output is on but the output cannot be controlled
due to an error between the logic area and the digital output. The LED does not mon-
itor the output state. In the event of an error, the actual output state may differ from
the state indicated by the LED.
Figure 9-2 Indicators on I/O terminals
Diagnostics The following states can be read on I/O terminals:
Status The status of the input or output can be read from the relevant yellow LED:
Additional diagnostic or status indicators can be found on the terminals. They are
described in the corresponding documentation.
1
2
D
1
2
D
1
3
2
4
1
2
1
2
1
2
1
2
D
(1)
Green LED Diagnostics (for meaning see page 94)
1, 2,
3, 4
(2)
Yellow LED Status of the input/output
ON: Corresponding input/output set
OFF: Corresponding input/output not set
For terminals with extended diagnostics
E1, E2,
E3, E4
Yellow LED The meaning depends on the terminal. It is described in the
terminal-specific data sheet, e.g.,:
Short circuit/overload of the initiator supply
Short circuit of an output
Diagnostic input error message
ON: An error has occurred
OFF: No error