Diagnostic and status indicators
6452_en_11 Phoenix Contact 95 / 188
9.1.3 Indicators on power and segment terminals
Figure 9-1 Possible indicators on power and segment terminals
Diagnostics The following states can be read on power and segment terminals:
On terminals with fuses, the green UM or US LED indicates that the main or segment
voltage is present on the line side of the fuse, meaning that if the green LED is on,
there is voltage on the line side of the fuse. If the red E LED is also on, the fuse has
blown or is missing and no voltage is applied after the fuse.
If the red E LED is on and the green D LED is flashing at 2 Hz on terminals with fuse
and diagnostics, there is no voltage present after the fuse.
Thus, a blown fuse is indicated by both diagnostic indicators (E and D).
1
2
US
E
SEG/F
US
1
SEG
UM
1
PWR IN
SEG-ELFSEG-ELF
E
D
3
2
Power terminal
UM (1) Green LED Supply voltage in the main circuit (for meaning see page 94)
Segment terminal
US (1) Green LED Supply voltage in the segment circuit (for meaning see
page 94)
Power terminal with fuse and diagnostics/
segment terminal with electronic fuse
D (3) Green LED Diagnostics (for meaning see page 94)
Also on terminals with fuse
E (2) Red LED Fuse status
ON: Fuse not present or blown
OFF: Fuse OK