9.1 Indicators on Inline terminals
9.1.1 Indicators on bus couplers and terminals with remote bus
branch
For the meaning of the diagnostic and status indicators of the bus coupler and the
terminals with remote bus branch, please refer to the corresponding
documentation.
9.1.2 Indicators available on different terminals in the Inline
system
Some indicators can be found on various terminals (see section below) and generally
have the same meaning:
UM Green LED Supply in the main circuit
ON: Supply present in the main circuit
OFF: Supply not present in the main circuit
US Green LED Supply in the segment circuit
ON: Supply present in the segment circuit
OFF: Supply not present in the segment circuit
D Green LED Diagnostics
ON: Data transmission active within the station
Flashing:
0.5 Hz:
(slow)
Communications power present,
data transmission not active within the station
2 Hz:
(medium)
Communications power present,
peripheral fault
(e.g., fuse has blown, voltage not present)
4 Hz:
(fast)
Communications power present,
error at the interface between previous and flashing terminal
(the terminals after the flashing terminal cannot be ad-
dressed).
(E.g., loose contact at the bus interface, terminal before the
flashing terminal has failed, another terminal was snapped on
during operation (not permitted))
OFF: Communications power not present