Electrical potential and data routing (Inline)
6452_en_11 Phoenix Contact 89 / 188
GND
(24 V DC area)
This potential jumper is ground for the main and segment circuits.
NOTE: Overload
Please note that the GND potential jumper carries the total current of the main and
segment circuits. The total current of the main and segment circuits must not ex-
ceed the maximum current carrying capacity of the potential jumpers (8 A). The
maximum current carrying capacity is determined not only by the potential jump-
ers, but also by the power/segment terminal used.
Calculate the current in the station. Refer to the data provided in the terminal-spe-
cific data sheets for your particular application.
The Project+ software provides support when calculating the currents (see Section
“Appendix: Software support” on page 176).
FE
(24 V DC area)
The FE potential jumper is connected to the grounded DIN rail via the FE spring at each
bus coupler, each 24 V power terminal, and each segment terminal and is led through all
subsequent 24 V terminals.
In addition, connect the FE connection to a grounding terminal at the bus coupler.
If the FE jumper is interrupted by a 120 V AC/230 V AC voltage level, reconnect the FE
connection to a grounding terminal at the subsequent 24 V DC power terminal.
Please also observe the information in Section “Grounding concept” on page 112.
FE spring
(24 V DC area)
This spring creates the FE contact between the bus coupler, a 24 V DC power terminal or
a segment terminal, and the grounded DIN rail.
Data routing
(all areas)
The bus signal is also transmitted within the station using a connection that is created au-
tomatically when the station devices are snapped on.
Current carrying capacity
(all areas)
The maximum total current flowing through the potential jumpers is limited. The maxi-
mum current carrying capacity for each circuit is specified in Section “Circuits and provi-
sion of supply voltages” on page 80.
Please also observe the information about the current carrying capacity of the pow-
er and segment terminals provided in the terminal-specific data sheets.
NOTE: Malfunctions
If the current carrying capacity of the potential jumpers U
L
or U
ANA
is reached, the
voltage must be boosted via a power terminal, or a new station must be created us-
ing a bus coupler
If the current carrying capacity of the potential jumpers U
M
, U
S
, and GND is reached
(total current of U
S
and U
M
), a new power terminal must be used.
The Project+ software provides support when calculating the currents (see Section
“Appendix: Software support” on page 176).