Phoenix Contact IB IL AO 4/U/0-10-ECO handleiding

190 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 84 van 190
IL SYS INST UM E
84 / 188 Phoenix Contact
6452_en_11
8.1.6 Mains voltage for power-level terminals
The mains voltage for power-level terminals is not provided via the potential jumpers. It
is either supplied to the power-level terminal via a power connector or led between di-
rectly adjacent power-level terminals via power bridges.
Voltage The mains voltage must have the following values:
Frequency The frequency of the mains voltage must be 50 Hz or 60 Hz.
Current carrying capacity The maximum current carrying capacity for the incoming mains must be 20 A. If this value
is reached, it must be reinjected.
IB IL 400 ELR ... IB IL 400 MLR ...
Nominal voltage during op-
eration (conductor voltage)
400 V AC 400 V AC
Voltage range 187 V AC ... 440 V AC + 0%
with safe isolation between
mains and SELV
187 V AC ... 519 V AC + 0%
with safe isolation between
mains and SELV;
187 V AC ... 600 V AC + 0%
with basic insulation be-
tween mains and SELV

Bekijk gratis de handleiding van Phoenix Contact IB IL AO 4/U/0-10-ECO, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPhoenix Contact
ModelIB IL AO 4/U/0-10-ECO
CategorieNiet gecategoriseerd
TaalNederlands
Grootte18677 MB