8.1.6 Mains voltage for power-level terminals
The mains voltage for power-level terminals is not provided via the potential jumpers. It
is either supplied to the power-level terminal via a power connector or led between di-
rectly adjacent power-level terminals via power bridges.
Voltage The mains voltage must have the following values:
Frequency The frequency of the mains voltage must be 50 Hz or 60 Hz.
Current carrying capacity The maximum current carrying capacity for the incoming mains must be 20 A. If this value
is reached, it must be reinjected.
IB IL 400 ELR ... IB IL 400 MLR ...
Nominal voltage during op-
eration (conductor voltage)
400 V AC 400 V AC
Voltage range 187 V AC ... 440 V AC + 0%
with safe isolation between
mains and SELV
187 V AC ... 519 V AC + 0%
with safe isolation between
mains and SELV;
187 V AC ... 600 V AC + 0%
with basic insulation be-
tween mains and SELV