Phoenix Contact IB IL AO 4/U/0-10-ECO handleiding
Handleiding
Je bekijkt pagina 73 van 190

Inline connectors
6452_en_11 Phoenix Contact 73 / 188
7.2 Connectors for the 24 V DC area
Connector types The following connector types are available for the 24 V DC area:
Figure 7-3 Connector types for Inline terminals
A Standard connector
The green standard connector is used for the connection of two signals in 4-wire
technology or 8 signals in 1-wire technology (e.g., digital I/O signals).
The black standard connector is used to supply the supply voltage. Some of the
adjacent contacts can be jumpered internally (see Figure 7-4 on page 74).
B Shield connector for connecting one cable
C Shield connector for connecting two cables
Green connectors B and C are used for signals connected using shielded cables
(e.g., analog I/O signals, high-frequency counter inputs, remote bus cable).
FE or shielding is connected via a shield connection clamp rather than via a
terminal point.
D Extended double signal connector
The green double signal connector is used for the connection of four signals in 3-
wire technology (e.g., digital I/O signals).
The black double signal connector is used to supply the supply voltage. Some of
the adjacent contacts can be jumpered internally (see Figure 7-4 on page 74).
A B C D