Inline product groups
6452_en_11 Phoenix Contact 47 / 188
2. Inline station with standard terminals, safety modules, and EX-IS terminals
Figure 5-15 Inline station with standard terminals and EX-IS terminals
Figure 5-16 Inline station with standard terminals, a safety module, and EX-IS termi-
nals
1 Inline bus coupler or Inline controller with integrated I/Os or without I/Os
2 Standard Inline terminals according to your application, without or with approval for
potentially explosive areas of Zone 2
3 Safety modules according to your application
4 IB IL EX PWR-ISO-PAC: isolator between the non-intrinsically safe Inline I/O expan-
sion and intrinsically safe Inline power supply
5 IB IL EX-IS PWR IN-PAC: Inline power terminal for supplying power to intrinsically
safe I/O terminals
6 IB IL EX-IS ...: intrinsically safe Inline I/O terminals according to your application
needs
In mixed stations, standard terminals including safety modules must only be used
before the isolator terminal.
Standard terminals must not be used after the EX-IS terminals.
2 4 61 5
2 4 61 53