DANGER: Explosion hazard
If at least one terminal in the Inline station does not have ATEX approval for Zone 2,
the entire station must not be installed in this area.
In this case, install the station in a safe area.
Not all bus couplers support the operation of intrinsically safe I/O terminals.
Table 5-6 on page 49 shows which bus couplers can be used in combination with
intrinsically safe I/O terminals.
Check if the terminals you use are ATEX approved for Zone 2. Conformity is ex-
plained in the CE Declaration of Conformity. In addition, the terminals are marked
accordingly.
For an overview of Inline terminals for use in Zone 2 potentially explosive areas,
please refer to the application note AH EN IL EX ZONE 2.
Table 5-4 Use of Inline terminals in potentially explosive areas
Inline terminal ATEX
approval
for Zone 2
Installation in
zone
Use of sensors/actuators
in zone
Safe 2 Safe 2 1 0
Inline bus coupler/Inline controller without I/Os – – – –
Inline bus coupler/Inline controller with I/Os
standard I/O terminals
Inline bus coupler/Inline controller without I/Os
Inline bus coupler/Inline controller with I/Os
standard I/O terminals
Intrinsically safe I/O terminals