Phoenix Contact IB IL AO 4/U/0-10-ECO handleiding
Handleiding
Je bekijkt pagina 163 van 190

Appendix: Inline: Additional information
6452_en_11 Phoenix Contact 163 / 188
A Appendix: Inline: Additional information
A 1 Use of Inline terminals at an elevation of more than
3000 meters
This section applies to terminals of the Inline product group that are operated with a DC
voltage of < 60 V DC.
WARNING: Dangerous contact voltage/loss of safety function
This section does not apply to the following modules or applications:
– Terminals that are not operated with PELV (Protective Extra Low Voltage) (e.g.
120 V or 230 V)
– Terminals with safety functions (e.g. SafetyBridge, Profisafe)
– Use of a safe signal path
– Use in potentially explosive areas (IEC Ex, ATEX, Hazardous Location).
– XC variants
In these cases, consider the individual terminal or application separately.
The Inline terminals are approved for use up to an elevation of 3000 m above sea level,
see “Technical data for Inline” on page 154.
The maximum permissible ambient temperature decreases at elevations above this level.
Therefore, keep temperature derating in mind when using the terminals at an elevation
greater than 3000 m up to 5000 m.
Figure A-1 Derating of the permissible ambient temperature depending on the oper-
ating elevation
Key:
T [°C] Maximum ambient temperature (operation) in °C
h [m] Elevation in m
70
0
60
50
40
30
20
10
55
T [°C]
0 1000 2000 3000 4000
5000
h [m]