Phoenix Contact IB IL AO 4/U/0-10-ECO handleiding

190 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 157 van 190
Inline: Technical data and ordering data
6452_en_11 Phoenix Contact 157 / 188
Conformance with EMC directive 2014/30/EU
This table provides standard data. For different values, please refer to the terminal-specific data sheets.
Noise immunity test in accordance with EN IEC 61000-6-2
Electrostatic discharge (ESD) IEC 61000-4-2 Criterion B
±6 kV contact discharge, ±8 kV air discharge
Electromagnetic fields IEC 61000-4-3 Criterion A, Field strength: 10 V/m
Fast transients (burst) IEC 61000-4-4 Criterion B
Remote bus: ±2 kV
Power supply: ±2 kV
I/O cables: ±2 kV
Criterion A
All interfaces: ±1 kV
Surge voltage IEC 61000-4-5 Criterion B
AC supply lines:
±1.0 kV/±2.0 kV (symmetrical/asymmetrical)
DC supply lines:
±0.5 kV/±1.0 kV (symmetrical/asymmetrical)
In accordance with EN 61131-2/IEC 61131-2:
No restriction
In accordance with IEC 6100-6.2:
Lines < 30 m that do not leave the building
Signal lines:
±1.0 kV/±1.0 kV (symmetrical/asymmetrical)
Conducted interference IEC 61000-4-6 Criterion A
Test voltage 10 V
Noise emission test in accordance with EN IEC 61000-6-4
Noise emission of housing Class A
Data transfer in the local bus
Protocol IEC 61158
Transmission speed 500 kbps or 2 Mbps
Transmission Inline data jumpers

Bekijk gratis de handleiding van Phoenix Contact IB IL AO 4/U/0-10-ECO, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPhoenix Contact
ModelIB IL AO 4/U/0-10-ECO
CategorieNiet gecategoriseerd
TaalNederlands
Grootte18677 MB