Phoenix Contact IB IL AO 4/U/0-10-ECO handleiding
Handleiding
Je bekijkt pagina 157 van 190

Inline: Technical data and ordering data
6452_en_11 Phoenix Contact 157 / 188
Conformance with EMC directive 2014/30/EU
This table provides standard data. For different values, please refer to the terminal-specific data sheets.
Noise immunity test in accordance with EN IEC 61000-6-2
Electrostatic discharge (ESD) IEC 61000-4-2 Criterion B
±6 kV contact discharge, ±8 kV air discharge
Electromagnetic fields IEC 61000-4-3 Criterion A, Field strength: 10 V/m
Fast transients (burst) IEC 61000-4-4 Criterion B
Remote bus: ±2 kV
Power supply: ±2 kV
I/O cables: ±2 kV
Criterion A
All interfaces: ±1 kV
Surge voltage IEC 61000-4-5 Criterion B
AC supply lines:
±1.0 kV/±2.0 kV (symmetrical/asymmetrical)
DC supply lines:
±0.5 kV/±1.0 kV (symmetrical/asymmetrical)
– In accordance with EN 61131-2/IEC 61131-2:
No restriction
– In accordance with IEC 6100-6.2:
Lines < 30 m that do not leave the building
Signal lines:
±1.0 kV/±1.0 kV (symmetrical/asymmetrical)
Conducted interference IEC 61000-4-6 Criterion A
Test voltage 10 V
Noise emission test in accordance with EN IEC 61000-6-4
Noise emission of housing Class A
Data transfer in the local bus
Protocol IEC 61158
Transmission speed 500 kbps or 2 Mbps
Transmission Inline data jumpers