Connecting cables
6452_en_11 Phoenix Contact 141 / 188
12.5.3 The various connection methods for sensors and actuators
1-wire technology Figure 12-8 1-wire termination for digital devices
Sensor Figure 12-9, detail A, shows the detection of a sensor signal schematically. The SW
switch provides the input signal. The sensor signal is led to terminal point IN1. The sensor
is supplied by the voltage U
S
.
NOTE: Malfunction due to potential shifts
Supply the sensors and U
S
of the Inline station from the same power supply. Make
sure that there is at least one common GND as reference potential.
This will prevent potential shifts, which can have undesirable effects on the function
of the station.
Actuator Figure 12-9, detail B, shows the connection of an actuator. The actuator is supplied by
output OUT1. The load is switched directly via the output.
NOTE: Malfunction due to potential shifts
Make sure that GND of the actuators and GND of the supply voltage U
S
, which sup-
ply the actuators, have the same potential.
This will prevent potential shifts, which can have undesirable effects on the function
of the station.
The following Inline terminals are designed to connect sensors and actuators in 1-
wire technology:
IB IL 24 DI8/HD-PAC, IB IL 24 DO8/HD-PAC
IB IL 24 DI8/HD-ECO, IB IL 24 DO8/HD-ECO
IB IL 24 DI 32/HD-PAC, IB IL 24 DO 32/HD-PAC
For connection examples, please refer to the corresponding data sheets.
IN1
OUT1
B
A
IN1
+24 V (U )
S
IN3
IN5
IN6
OUT3
OUT5
OUT6
SW