Mounting/removing devices
6452_en_11 Phoenix Contact 125 / 188
11.5.3 Order of the Inline terminals
11.5.3.1 General order
The order of the terminals within an Inline station should depend on the current con-
sumption of the I/O from the potential jumpers U
M
and U
S
.
As the voltage at every power terminal is reinjected into the potential jumpers U
M
and U
S
,
the section (main circuit) between a bus coupler and a power terminal or between a
power terminal and another power terminal must always be considered when calculating
the current. If power terminals are not used, the entire station is a main circuit.
Within a main circuit, install the terminals according to their current consumption. In-
stall the terminals with the highest current consumption first. This has the advantage that
the high supply current does not flow through the entire main circuit and thus does not
flow through all the terminals.
The following order is recommended.
Please also observe the following notes:
– In the event of any further restrictions regarding the position of a terminal, please re-
fer to the terminal-specific data sheet.
– For the current consumption of the terminals, please refer to the relevant terminal-
specific data sheet.
Table 11-1 Order of the Inline terminals within a main circuit
Function Abbreviation in order
designation
Function identi-
fication
Note
1 Digital output DO, SDO Pink, red,
dark red
In descending order of current consumption
2 Digital input DI, SDI Light blue, blue,
dark blue
In descending order of current consumption
3 Relay DOR, SDOR Dark red
4 Power ELR, MLR,
EC AR, DC AR
Dark red See 11.5.3.4
5 Special functions Orange In descending order of current consumption
– Open and
closed-loop
control
PWM, CNT,
SSI, INC, TEMPCON
– Communication RS, ASI MA, DALI
– Detection INC-IN, SSI-IN,
IMPULSE-IN
– Safety SAFE Please observe any special requirements
(subsequent safety-related segment circuit or
subsequent power-level terminals).
6 Analog output AO Yellow In descending order of current consumption;
see 11.5.3.3
7 Analog input AI, SGI, TEMP Green In descending order of current consumption;
see 11.5.3.3
IB IL TEMP 2 UTH-PAC As the last terminal