Mounting/removing devices
6452_en_11 Phoenix Contact 119 / 188
Figure 11-12 Mounting a terminal
Removal When removing a terminal, proceed as shown in Figure 11-13 on page 120:
Disconnect the power to the station.
If there is a labeling field, which covers several connectors, it may have to be re-
moved (detail A1).
If a terminal has several connectors, all connectors of the terminal must be re-
moved. The following describes how a 2-slot terminal is removed.
Lift the connector of the terminal to be removed by pressing on the back connector
shaft latching (detail A2).
When using extended double signal connectors (long connectors), please ensure
that you do not bend them back too far, as you may break the front snap-on mech-
anism.
Remove the connector (detail B).
Remove the adjacent connectors of the neighboring terminals (detail C). This pre-
vents the potential routing knife contacts and the keyway/featherkey connections
from being damaged. You also have more space available for accessing the terminal.