Phoenix Contact IB IL AO 4/U/0-10-ECO handleiding
Handleiding
Je bekijkt pagina 119 van 190

Mounting/removing devices
6452_en_11 Phoenix Contact 119 / 188
Figure 11-12 Mounting a terminal
Removal When removing a terminal, proceed as shown in Figure 11-13 on page 120:
• Disconnect the power to the station.
• If there is a labeling field, which covers several connectors, it may have to be re-
moved (detail A1).
If a terminal has several connectors, all connectors of the terminal must be re-
moved. The following describes how a 2-slot terminal is removed.
• Lift the connector of the terminal to be removed by pressing on the back connector
shaft latching (detail A2).
When using extended double signal connectors (long connectors), please ensure
that you do not bend them back too far, as you may break the front snap-on mech-
anism.
• Remove the connector (detail B).
• Remove the adjacent connectors of the neighboring terminals (detail C). This pre-
vents the potential routing knife contacts and the keyway/featherkey connections
from being damaged. You also have more space available for accessing the terminal.
D
D1
D2
A
B
B1
B2
C1
C2
C
Bekijk gratis de handleiding van Phoenix Contact IB IL AO 4/U/0-10-ECO, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Phoenix Contact |
| Model | IB IL AO 4/U/0-10-ECO |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 18677 MB |







