Mounting/removing devices
6452_en_11 Phoenix Contact 115 / 188
11.4 Shielding concept
Shielding is used to reduce the effects of interference on the system.
11.4.1 Inline shielding concept
In the Inline system, shielded cables are used with the following terminals:
Remote bus cables
Connecting cables
At terminals for analog signals (analog input, analog output, temperature record-
ing)
At terminals for open and closed-loop control
At communication terminals
At detection terminals
At programmable terminals
Observe the following points when installing shielding:
Secure the shielding so that as much of the braided shield as possible is held under-
neath the clamp of the shield connection.
Make sure there is good contact between the connector and base.
Do not damage or squeeze the wires.
When connecting the shielding, observe the specifications for the connector wiring.
11.4.2 Shielding when connecting analog sensors and actuators
Always connect analog sensors and actuators with shielded, twisted pair cables.
Connect the shielding via the Inline connector with shield connection (see Section
“Connecting shielded cables using an Inline shield connector” on page 129).
When connecting the cables, observe the instructions in the terminal-specific data
sheets.
As a rule, shielding must only be connected directly to the PE potential on one side.
This is to prevent any occurrence of voltage equalization currents via the shielding.
If necessary, integrate the shielding concept for analog I/O cables into the system
concept. For example, use a central FE shield connection at the control cabinet entry.