Mounting/removing devices
6452_en_11 Phoenix Contact 105 / 188
11 Mounting/removing devices
11.1 Basic information about mounting
Mounting location Modules and terminals of the Inline product range have IP20 protection and are therefore
designed for use in a closed control cabinet or control box (terminal box) with IP54 pro-
tection or higher.
DIN rail Install Inline Block IO modules and Inline terminals on a DIN rail with the following prop-
erties.
– 35 mm standard DIN rail (see “General accessories” on page 162)
– DIN rail height: 7.5 mm
– Mounted on a level surface
If these requirements are met, the module or terminal rests on the mounting surface.
Figure 11-1 Level surface with a DIN rail height of 7.5 mm
The distance between DIN rail fasteners must not exceed 200 mm. This distance is nec-
essary for the stability of the rail when mounting and removing devices.
Figure 11-2 Fixing the DIN rail (dimension in mm)
7.5
200