Startup, restart after replacing, and parameterizing the safe PROFINET gateway
8220_en_06 PHOENIX CONTACT 85
C 3 Startup, restart after replacing, and parameterizing
the safe PROFINET gateway
Checklist for startup, restart after replacing, and parameterizing the
FL PN/PN SDIO-2TX/2TX safe PROFINET gateway
Device type/equipment identification
Version: HW/FW Date
Test engineer 1 Test engineer 2
Remark
No. Requirement (mandatory) Ye s Remark
1 Was startup completed according to the specifications (specifications
from the planning phase and according to the user manual)?
2 Is it ensured that when the supply voltage of the FL PN/PN SDIO-2TX/
2TX is switched on, the PROFIsafe devices involved in the safety
function cannot present any danger?
3 During startup, is it ensured that any person starting hazardous
movements intentionally can only do so with a direct view of the danger
zone?
4 Are safety distances that must be observed calculated according to the
response and delay times implemented?
5 Does the parameterization of the address settings/process data settings
and the declaration of the variables correspond to the planned
application?
Date Signature (test engineer 1)
Date Signature (test engineer 2)