Technical data and ordering data
8220_en_06 PHOENIX CONTACT 63
Ambient conditions
Degree of protection IP20 (EN 60529:1991)
Pollution degree 2, when installed in housing or a control cabinet with IP54
protection or higher
Air and creepage distances According to IEC 60439-1
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Permissible temperature (operation) -2C to +6C
Permissible temperature (storage/transport) -25 °C to +70 °C
Permissible humidity (operation) 10 % to 85 %, no condensation
Permissible humidity (storage/transport) 10 % to 85 %, no condensation
Permissible air pressure (operation) 80 kPa to 108 kPa (up to 2000 m above sea level)
Permissible air pressure (storage/transport) 66 kPa to 108 kPa (up to 3500 m above sea level)
To ensure correct operation, the safe PROFINET gateway must be installed in housing or a control cabinet
with a minimum of IP54 protection.
Mechanical requirements
Shock according to EN 60068-2-27/IEC 60068-2-27
(Operation/storage/transport)
15g
Vibration resistance in accordance with EN 60068-2-6/
IEC 60068-2-6
(Operation/storage/transport)
5g
Time characteristics of PROFIsafe
WCDT
copy
4ms
DAT 5ms
Safety characteristics according to IEC 61508/EN 61508
Safety Integrity Level (SIL) 3, maximum
Probability of a dangerous failure on demand by the safety
function (PFD
AVG
, low demand mode)
1 x 10
-5
Probability of a dangerous failure per hour for the entire
module (PFH, high demand mode)
1 x 10
-9
Hardware fault tolerance (HFT) of the module 1
Permissible duration of use 20 years