ECM – multifunctional current measuring transducers
30 / 78 Phoenix Contact
111433_en_00
4.1.5.3 Method: Sliding interval
Figure 4-8 Average value over sliding interval
Interval
Specify the duration of the measurement interval in seconds from which the current and
frequency average values (AVG) are calculated.
The average value is calculated over a fixed time interval (e.g., 900 seconds).
The duration of the interval is divided by the number of partial intervals (inte-
ger). Updating takes place at the end of each partial interval.
In this case, the duration of the individual partial intervals is automatically de-
termined by the measuring transducer.