Table 3-1 Connection assignment for ECM-UC-10(0)A-UI(-REL)
Connection
terminal block
Signal Description
2.1 +24V Operating voltage
2.2 +24V Operating voltage
2.3 GND1 Reference ground for operating voltage
2.4 GND1 Reference ground for operating voltage
Terminal blocks 3.1 ... 3.4 only apply to ECM-UC-...-UI-REL
3.1 11 Center contact: Relay
3.2 14 N/C contact: Relay
3.3 12 N/O contact: Relay
3.4 Not used
4.1 U/I Current and voltage output
4.2 U/I Current and voltage output
4.3 GND2 Reference ground for current and voltage output
4.4 GND2 Reference ground for current and voltage output
Terminal blocks 5.1 ... 5.4 only apply to ECM-UC-...-UI-REL
5.1 DO+ Digital output: Transistor collector
5.2 DO- Digital output: Transistor emitter
5.3 DI+ Digital input
5.4 DI- Digital input
Terminal blocks 6.1 ... 6.4 only apply to ECM-UC-10A-UI(-REL)
6.1 0.1 A/1 A Input for current measurement range
6.2 5 A Input for current measurement range
6.3 10 A Input for current measurement range
6.4 GND Reference ground for inputs for current measure-
ment ranges