CONTACTRON Speed Starter
96 / 150 Phoenix Contact
109908_en_02
ID Display on the control panel Error name Error descriptions
3 OV - Over voltage error Overvoltage (ov) DC link voltage has exceeded the
threshold for overvoltage
Reset
Reset method Manual reset
Reset condition Reset only when the DC link voltage is lower than the reset
level.
230 V AC models:
150 V AC ... 240 V AC input: >210 V DC
110 V AC ... 149 V AC input: >105 V DC
480 V AC models:
300 V AC ... 480 V AC: >420 V DC
220 V AC ... 299 V AC: >210 V DC
Cause Remedial measures
Deceleration time is too short, causing excessive
regenerative energy of load.
Increase the ramp time (“RAMP”).
Replace the CONTACTRON Speed Starter with a more
powerful model.
Mains voltage is too high. Check the mains voltage.