Warning codes
109908_en_02 Phoenix Contact 93 / 150
11 Warning codes
If a warning is shown on the device, the “PWR/STO/ERR” LED flashes red. In the event of
an STO warning, the “PWR/STO/ERR” LED flashes green.
ID Display on the control panel Warning name Description
1 UV under voltage warning Undervoltage (UV) DC link circuit under warning level
Tripping and reset
Tripping condition for warning 230 V AC models:
150 V AC ... 240 V AC input: <195 V DC
110 V AC ... 149 V AC input: <100 V DC
480 V AC models:
300 V AC ... 480 V AC: <390 V DC
220 V AC ... 299 V AC: <195 V DC
Tripping time Immediate tripping when the DC link circuit voltage is lower
than this level.
Reset method Auto
Reset condition Automatically reset when the DC link circuit voltage is higher
than the reset level.
230 V AC models:
150 V AC ... 240 V AC input: >210 V DC
110 V AC ... 149 V AC input: >105 V DC
480 V AC models:
300 V AC ... 480 V AC: >420 V DC
220 V AC ... 299 V AC: >210 V DC
Cause Remedial measures
Power failure Improve the power supply conditions.
Power voltage changes Adjust the voltage of the CONTACTRON Speed Starter’s power
range setting.
Motor start with large capacity Check the load.
Increase the power of the power supply devices.
Load is too large. Reduce the load.
Increase the CONTACTRON Speed Starter’s capacity.
Increase the acceleration time.