Phoenix Contact CSS 1.5-1/3-EMC handleiding

152 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 80 van 152
CONTACTRON Speed Starter
80 / 150 Phoenix Contact
109908_en_02
10.5.2 Motor rated voltage
Set the value in accordance with the rated voltage of the motor as specified on the
motor’s rating plate.
NOTE: Device damage possible
When operating the device with single-phase mains input with at least 200 V AC,
you must not set the motor voltage to 110 V AC in the OPTIONS menu.
Otherwise, the device could be damaged.
When 110~120 (220~240) V is set, half voltage mode will be activated.
10.5.3 Highest output frequency
Set this parameter to determine the maximum value of the SPEED1 and SPEED2 fre-
quency command.
Can be set
during
operation
Clear text display Parameter name Setting range Default setting
- 2. rv - motor rated voltage Motor rated voltage 230 V models: 110 V ... 240 V
(1-phase input)
480 V models: 220 V ... 480 V
(3-phase input)
230 V AC
400 V AC
Can be set during
operation
Clear text display Parameter name Setting range Default setting
- 3. hF - highest
output frequency
Highest output frequency 0.0 Hz ... 500.0 Hz 100.0 Hz

Bekijk gratis de handleiding van Phoenix Contact CSS 1.5-1/3-EMC, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPhoenix Contact
ModelCSS 1.5-1/3-EMC
CategorieNiet gecategoriseerd
TaalNederlands
Grootte11973 MB