Phoenix Contact CSS 1.5-1/3-EMC handleiding
Handleiding
Je bekijkt pagina 75 van 152

Description of parameter settings
109908_en_02 Phoenix Contact 75 / 150
10 Description of parameter settings
10.1 Rotary switch in “CURRENT” position
The CONTACTRON Speed Starter features integrated full motor protection. The device
has an integrated tripping characteristic (see Figure 10-1). If the load of the motor is
higher than the nominal current, the device will trip according to this curve. Additionally,
the device has an integrated thermal memory. This means that in case of a high load, the
curve will be loaded up and leads to a faster tripping time. The tripping of the device is
dependent on the frequency. A low frequency leads to a quicker load of the thermal mem-
ory and a high frequency will react slower.
Figure 10-1 Tripping characteristic
Can be set during
operation
Clear text
display
Parameter name Setting range Default setting
- Motor rated current 0.1 ... rated current of the
CONTACTRON Speed Starter
Rated current of the
CONTACTRON Speed Starter
1,00
10,00
100,00
1000,00
100 150 200 250 300 350 400 450 500 550 600 650 700 750
Motor rated current [%]
Tripping time [s]