Phoenix Contact CSS 1.5-1/3-EMC handleiding

152 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 133 van 152
Operational limitations
109908_en_02 Phoenix Contact 133 / 150
A 6 Operational limitations
Table A-8 Operational limitations
Characteristic Operating environment
Operating
temperature
If the CONTACTRON Speed Starter operates at the rated cur-
rent, the ambient temperature must be between -20°C ... 55°C.
If the temperature is above 55°C, decrease 2.5% of the rated
current for every 1°C increase in temperature. The maximum al-
lowable temperature is 60°C.
Installation altitude If the CONTACTRON Speed Starter is installed at an altitude of
0 m ... 1000 m, normal operational limitations apply. For alti-
tudes of 1000 m ... 2000 m, decrease the Speed Starter’s rated
current by 1% or lower the temperature by 0.5°C for every
100 m increase in altitude. If installing at an altitude higher than
2000 m is required, contact Phoenix Contact for more informa-
tion.
Impulse voltage
insulation
6 kV
Safe mains isolation by double/reinforced insulation between
power electronic and control electronic (IEC/EN 61800-5-1)
Leakage current >3.5 mA AC, >10 mA DC (IEC/EN 61800-5-1)