Error codes
109908_en_02 Phoenix Contact 101 / 150
ID Display on the control panel Error name Error descriptions
13 Th1o - Temperature detection error IGBT temperature detection failure (tH1o) IGBT hardware cannot
detect the temperature
anymore.
Reset
Reset method Manual reset
Cause Remedial measures
Hardware failure Return to the factory for repair.
System is operated below -20°C Check the ambient conditions.
ID Display on the control panel Error name Error descriptions
14 Ot - TC over temperature Overtemperature (ot) Overtemperature if the thermal contact mon-
itoring parameter is set to tconc or tcono.
The TC input voltage is <2 V (tconc) or >5 V
(tcono).
Reset
Reset method Manual
Reset condition Reset when input voltage is >5 V (tconc) or <2 V (tcono).
Cause Remedial measures
Motor shaft is blocked. Remove the blockage.
Check the drive layout.
Check the mechanics of the motor.
Load is too large. Reduce the load.
Increase the motor power.
Check the drive layout.
Check the mechanics of the drive system.
Ambient temperature of the motor too high Change the installation location if there are heat sources in the
surroundings.
Install/add a cooling fan or air conditioner to lower the ambient tempera-
ture.
Motor cooling system fault Check the cooling system to clear the fault if there is any.