Phoenix Contact CSS 0.55-1/3 handleiding
Handleiding
Je bekijkt pagina 26 van 152

CONTACTRON Speed Starter
26 / 150 Phoenix Contact
109908_en_02
Figure 4-5 Derating curve
NOTE:
The installation direction for side mounting is different than for other installation
methods. Therefore, the minimum mounting clearances A ... C indicate different
sides of the CONTACTRON Speed Starter, as shown in the figures below.
Table 4-2 Minimum mounting clearances
Installation type A
[mm]
B
[mm]
C
[mm]
Ambient temperature [°C] Derating
curve
Max. (without
derating)
Max. (with
derating)
Single installation 50 30 - 55 60 a
Side-by-side horizontal installation 50 30 30 55 60 a
Installation without clearance (except for
CSS 0.55-3/3)
50 30 0 45 60 b
Installation without clearance for CSS 0.55-3/3 50 30 0 40 60 c
Side mounting (except for CSS 0.55-3/3) 50 0 0 45 60 b
Side mounting for CSS 0.55-3/3 50 0 0 40 60 c
Ambient temperature [°C]
Output current rating [%]
Curve a
Curve b
Curve c