CONTACTRON Speed Starter
48 / 150 Phoenix Contact
109908_en_02
7.2 Standard fuses and circuit breakers (for UL and cUL)
You can choose either fuses or circuit breakers for branch circuit protection (BCP)
according to your needs. Refer to the following specifications for details.
The standard fuses and circuit breakers (for UL and cUL) have been tested in accordance
with UL 61800-5-1.
NOTE:
When a single motor is installed and the rated current of the fuse is >400% of the
motor current (full load amps), the fuse value has to be calculated.
If the calculated value is between two standard ratings, the nearest standard rating
less than the calculated has to be used.