Maintenance
109484_en_01 PHOENIX CONTACT 71 / 94
7.4.1 Maintenance schedule
Perform a general visual inspection.
Check the switching devices and accessible printed circuit boards for traces of
smoke.
Remove any foreign objects.
Remove coarse dirt from the inside and outside of the system.
Remove any foreign objects.
Check the terminal points.
Check the connections.
Ensure that the screws are tight.
Tighten the screws at the contact points.
Check the filter mats and replace them, if necessary.
Check the functional condition of the system.
Check all parameters in the system.
Check all messages and alarms to the transfer terminal block of the system.
Thoroughly document all maintenance results.
Check the capacitors. Determine the capacitor capacities and compare them to the rat-
ed data.
7.4.2 Maintenance interval
To increase system reliability, we recommend scheduled maintenance.
We recommend to have manufacturer perform annual maintenance.
We recommend to check and, if necessary, replace the following components and
equipment according to the specified intervals.
Table 7-1 Maintenance interval
Maintenance work and checks Maintenance inter-
val (recommended)
Clean the ventilation openings depending on the conditions on site. Clean more often, if neces-
sary.
12 months
Check the cable connections for secure seating and retighten them, if necessary. Check the ter-
minal blocks and insulation for discoloration or changes. Replace damaged cable connections
and corroded contact elements.
12 months
Check the warning labels. 12 months
Perform a visual inspection of the existing fuses, insulators and contacts. Replace damaged parts. 12 months
Check the control and auxiliary voltages and messages. 12 months
Check the components, e.g., fans, as a preventive measure. 12 months
Check the covers and function of the locking mechanisms. 12 months