13. Conguration menu (cont.)
Password
Version
Factory reset
‘Dead band’
0.0 to 100.0%
• at the ‘Dead band’ (d.bnd) parameter set a value between ‘0.0’ %
and ‘100.0’ %. This is a percentage of the ‘input signal high’ parameter
congured at the ‘Advanced scaling’ section. Input signals below this
value, are treated as a ‘0’.
example : instrument congured with code ‘011’ (0/10 mVdc = 4/20 mA)
and ‘input signal high’ parameter modied to 8 mVdc for an effective
input - output relation of ‘0/8 mVdc = 4/20 mA’. Congure the ‘Dead band’
parameter to ‘1.0’ to set a dead band value of 0.08 mVdc. All signals below
0.08 mVdc will be treated as 0 mVdc, and the output will be 4 mA.
• the ‘Version’ (VEr) parameter informs about the rmware version
running in the instrument.
• at the ‘Password’ (PASS) parameter dene a 4 digit code to
block access to the ‘conguration menu’. Activate the password to
prevent access to the instrument conguration by non authorized
personnel. To activate the ‘Password’ function select ‘on’, enter the
code and validate. The password will be requested when accessing
the ‘conguration menu’. The password does not block access to the
‘force’ menu. To deactivate the password, set the parameter to ‘oFF’.
• at the ‘Factory reset’ (FAct) parameter select ‘yes’ to activate the
default factory conguration (see section 15 for a list of factory
default parameters).