PANDUIT UPS INSTALLATION MANUAL
10
• It is recommended to mount the UPS and EBP unit near the bottom of the rack
due to the physical weight of these units.
Installation
• The UPS system must be installed in an environment with a temperature range
from 0°C to 40°C.
• The UPS system must be installed in an environment with a humidity from 20%
to 90% RH, non-condensing.
• The UPS system may be installed in an environment with an altitude of 1000
meters (3,281ft.) or lower with no derating. Derate 1% for every 100 meters
above 1000 meters per IEC 62040-3. This is an example of power derating
according to altitude:
Altitude (m)
1000
2000
2500
3000
3500
4000
4500
5000
Load
coefficient
100%
90%
85%
80%
75%
70%
65%
60%
• Most UPS system units with battery cartridges are heavy and may require a lift to
install in the rack/cabinet.
• Each power input on the UPS unit must be protected by a branch circuit
protective device rated for the UPS specified on the product rating label.
• Pluggable UPS systems may be installed and operated by a trained qualified
layperson.
• Connect the UPS system only to an earth-grounded outlet that is easily
accessible and close to the UPS system.
• Permanently wired UPS systems must be installed and wired by trained qualified
electricians only.
• For permanently connected UPS systems, ensure source power is off and locked
out before installing permanently wired connections to the UPS disconnect
device or UPS system.
• For permanently connected UPS systems, a readily accessible disconnect device
should be incorporated external to the UPS system.
• For permanently connected UPS systems, each power input on the UPS systems
must be wired with the appropriate wire gauge for the system being installed.
Refer to Section 4 – Electrical Connections in this document.
• For permanently connected UPS systems, check for hazardous voltages
between terminals before wiring.
• For permanently connected UPS systems, ensure that cover plates on all units
are installed before providing power to the UPS system.
• Ensure that all units in the UPS system (includes UPS, EBP, MBS, etc.) are
properly grounded before power is applied to the system, refer to Section 4 –
Electrical Connections in this document.
• It is recommended to install external isolators on the UPS system to prevent
back-feed on the input from the battery if an internal UPS fault occurs.