Operation statuses
Status
LED indicators
Alarm Description
ALARM
LED
(red)
CHECK
LED
(orange)
POWER
LED
(green)
Blinking
interval
Normal
No Status is normal.
Preparing
(Initial
communication)
1 second
No
The unit is preparing to
operate.
Leak detected
(Currently
leaking)
0.5
seconds
Yes
Refrigerant is leaking.
Immediately ventilate the area
and evacuate from the room.
Also immediately contact the
manager of the facility and
the place of purchase or the
authorized service centre.
Leaks recorded
1 second
No
A refrigerant leak was
detected in the past.
The refrigerant sensor
is characteristically less
responsive to refrigerant after
it has detected refrigerant
once and it will require
maintenance. Immediately
contact the manager of
the facility and the place of
purchase or the authorized
service centre.
Service life
of refrigerant
sensor
exceeded
1 second
alternately
No
The refrigerant sensor
installed in the indoor unit has
reached the end of its service
life. Immediately contact the
manager of the facility and
the place of purchase or the
authorized service centre to
request replacement of the
refrigerant sensor.
: On : O󰀨 : Blinking
The LEDs light as follows according to the status.
Descriptions of the LED indicators
(Continued on following page)